Basic
Residential Building Planning
Please
review these requirements prior to submitting your Permit Application to be
sure that your plans include all of the following items
DESIGN
CRITERIA:
Buildings
and structures must be built to safely support all loads as provided by the
International Residential Code. The
minimum design loads required for structures are listed in the following table:
|
Snow
Load (1) |
Wind
Speed (mph) |
Seismic
Design Cat. |
Frost
Line Depth |
Winter
Design Temp. |
|
30
to 35 |
60 |
A
|
42 |
0°F |
Note 1: 30
at elevations under 1700 feet
35 at elevations over 1700 feet
All habitable rooms must be provided with windows that are a minimum of 8% of the floor area, with an openable area of at least 4%.
Each
bedroom must have at least one emergency/escape window with a minimum opening
area of 5.7 sq. ft. with a minimum clear height of not less than 24 inches and a
clear width of 20-inches. The
window must be not more than 44-inches above the floor.
Note:
All windows installed where the bottom of the window is more than 72-inches
above the finished outside grade must be located and installed so that the
inside bottom of the window is not less than 24-inches above the floor.
Like
habitable rooms, bathrooms are also required to be provides with natural light
and ventilation. When natural light
& ventilation are not assessable, mechanical ventilation and artificial
light can be used. When mechanical
ventilation is used, air must be moved at a minimum of 50cfm to outside air.
Air ventilated from a bathroom or kitchen cannot be discharged into an
attic area.
LIGHTING
OUTLETS:
At
least one wall switched-controlled lighting outlet must be installed in the
living, cooking, sleeping and bathroom areas.
At
least one wall switched light outlet must also be installed in all hallways,
stairway, and attached and detached garages when supplied by electric power.
A
wall switched light, or an automatically controlled light, must be installed to
provide illumination on the exterior side of each door opening (except garage
doors).
An
attic or storage area must be illuminated by as switched lighting outlet when
the area contains equipment that may require servicing.
POWER
DISTRIBUTION:
Electrical
receptacles must be installed in every room of a dwelling unit.
All outlet receptacles must be tamper-resistant.
REQUIRED
BRANCH CIRCUITS:
Two
or more 20-amp circuits must be provided to serve receptacles in the
kitchen, pantry or breakfast /dining area.
Outlets
that serve the countertops, including islands, must be GFCI protected and
installed so that no point along the countertop is more than 24-inches from
an outlet (4-feet apart) and not more than 20-inches above the
countertop.
Receptacles
for specific built-in appliances (disposal, dishwasher, trash compactor,
refrigerator) cannot utilize these two required circuits.
One
20-amp circuit is required for the laundry area.
One
20-amp GFCI circuit to supply outlets in the bathroom.
At least one GFCI outlet must be installed within 36-inches of the
outside edge of the sink basin.
Other
required branch circuits are required based on the total computed load.
Outlets from these circuits are required to be installed at the
following locations:
Outdoor
GFCI outlets must be installed at the front and back of each dwelling unit
as well as within the perimeter of each deck or patio.
Laundry
areas shall have at least one outlet.
Unfinished
basements and garages shall have at least one GFCI protected outlet.
Hallways
of 10 feet or longer shall have at least one receptacle.
Furnace
and HVAC equipment
Arc-fault
circuit interrupters (AFCI) combination type breakers shall protect all
branch circuits that supply power all habitable spaces (Includes family rooms,
bed rooms, dining rooms, dens,
hallways, & closets.).
Receptacles
must be installed through the homes so that no point along any wall space
greater than 2-feet in width is more than 6-feet from a receptacle outlet.
(12 apart)
There
is no height requirement for placement of the outlets except that any receptacle
installed over 5 ½ feet from the floor and outlets installed in a floor are not
counted towards the minimum required.
STAIRWAYS:
All
interior and exterior stairways must be illuminated, including the landings and
treads.
Stairway
tread/riser maximum riser height shall
be 8 1/4 inches and the minimum tread depth shall be 9 inches +/- 3/8.
A 1 - 1 ½-inch nosing shall be provided on stairways with solid
risers. Stairways must be 36 wide.
Installing
a light in the vicinity of each landing can illuminate the stairways.
Stairs to a basement must have a light near the bottom of the stairs.
A
light switch must be installed at the top AND bottom of each set of stairs.
(This is only requirement for a 3-way switch installation.)
A
stairway must have minimum headroom of 68 as measured from the tread nose.
Handrails: The Code requires that a 1 Ό to 2 diameter handrail,
not less than 34 and 38 in height, be provided on at least one side of any
stairway that has four or more risers, including basement steps from the
outside.
A
handrail must be continuous from top to bottom. The ends of the handrail must not be more than 1 ½ from
the wall edge.
Guard
Rails:
Stairways, porches, decks, and balconies located more than 30-inches
above the floor shall have guards not less than 36 in height installed on the
entire structure. (34 for stairs 30 or more above the floor)
These
guards and stair rails must be constructed such that the spindles, rails, or
other type of ornamental pattern will not allow a 4-inch sphere to pass through
it. A 6-inch sphere cannot pass
through the open area formed by the riser, tread, and bottom of the rail.
REQUIRED
HEATING:
All
habitable areas of a dwelling must have fixed means to maintain the dwelling at
68°F.
INSULATION
REQUIREMENTS:
|
Maximum U-Factor: |
|
|
Windows & Doors |
Skylights |
|
0.35 |
0.60 |
Minimum Insulation R-Value:
|
Roof
/ Ceiling |
Framed Walls |
Mass Walls |
Basement
Walls |
|||
|
R-49 |
R-20 |
R-15 |
R-15
/19 |
|||
|
|
|
|
|
|||
|
Crawl
Spaces |
Slab
Perimeter |
Floors |
|
|||
|
R-10
/ 13 |
R-10
(4) |
R-21 |
|
|||
MOISTURE
VAPOR RETARDERS:
In
all framed walls, floors, and roof/ceiling assemblies that form the outside of
the structure, a vapor barrier shall be installed on the warm in winter side of
the insulation.
SEALING
OF THE BUILDING ENVELOPE: The
buildings must be sealed (caulked) to limit outside air infiltration.
The following areas must be caulked, weather stripped, or otherwise
sealed: all joints between walls, floors and ceiling assemblies, knee walls,
attic hatches, utility penetrations, openings between windows and door
assemblies and their jambs and framing, and walls between a garage and dwelling.
MINIMUM
ROOM AREAS:
Every
dwelling unit shall have at least one room that has not less than 120 Sq. Ft of
gross floor area. All other rooms
must be at least 70 sq. ft. of gross floor area.
There is no minimum floor area for a kitchen.
All
habitable rooms, including basements, must not be less than 7-feet in height, as
measured from the finished floor to the finished ceiling.
EMERGENCY
ESCAPE OPENINGS:
All
basements must have at least one 36 emergency escape door.
This door cannot open
into an attached garage.
A door may exit into a garage, but there then there must be a second door
to provide for the emergency exit from the basement without traveling through
the garage.
Each
sleeping area (bedroom) located in a basement shall have at least one openable
emergency escape and rescue opening. At
a minimum, this opening must be 20 wide and 24 high. THESE
DOORS OR WINDOWS MUST EXIT DIRECTLY TO AN OPEN AREA OUTSIDE THE BUILDING.
When
this opening is located below-grade, an approved exit ladder must be installed.
EGRESS:
Hallways:
The minimum width of a hallway is three (3) feet.
Doors:
At least one side-hinged door must be installed that is not less than
three (3) feet in width and 6-feet 8-inches in height that exits to a clear and
open area. Other doors that may be
installed are not required to meet this requirement.
A
36 landing, not more than 1 ½
lower than the top of the threshold, shall exist on the exterior of each door.
SANITATION:
Each
dwelling unit must have a kitchen area provided with a sink.
Unless
a dwelling is served by a vault privy (outhouse) and a portable water supply
does not exist, every dwelling unit must be provided with at least one toilet, a
bathroom sink, and a bathtub or shower.
All
plumbing fixtures must be connected to an approved sewage or sewer system.
GARAGES
& CARPORTS:
Openings
from an attached garage or carport directly into a room used for sleeping are
strictly prohibited.
Other openings between the garage and the residence shall be equipped
with solid 1 3/8 wood doors or hollow steel doors rated at a 20-minute fire
rating or better.
Windows
are not permitted in a wall separating an attached garage from a residence.
An
attached garage must be separated from the residence, and its attic area, by
a firewall constructed of ½ gypsum board applied on the garage side.
Duct
work is permitted to penetrate a wall between a garage and the residence when
the ducts are # 26 gauge sheet metal and the openings are sealed with a
fire-stopping material. Other penerations (wiring, piping) must be sealed with an
approved material.
When
the attached garage is located below a habitable room the ceiling of the garage
must be 5/8 Type X gypsum board. The
structures that supports a garage ceiling, the outside walls, must also be
protected by ½ drywall.
Carports
must be open on at least two (2) sides.
A carport that is not open on at least two sides is considered a garage.
Any
fuel burning appliances located in a garage must be located so that the source
of ignition is not less than 18-inches from the floor of the garage.
This includes wood & oil burners and gas furnaces.
SMOKE
ALARMS:
All
smoke alarms must be hard wired and interconnected in such a manner that when
one alarm is activated, all alarms in the dwelling will also be activated.
Smoke
alarms are required to be placed in each sleeping room, one just outside of the
sleeping area in the vicinity of the bedrooms, and an additional alarm on each
floor level of the dwelling, including the basement.
CARBON
MONOXIDE ALARMS
are required to be installed on the outside of each sleeping area (not in each
bedroom) and located in the immediate vicinity of the bedroom.
FOUNDATIONS
& DRAINAGE:
All
footings must be at least 6-inches thick and shall extend to a depth below the
frost line. For dwellings located in Elk or Cameron County, houses with a full
basement or manufactured housing with approved skirting, the bottom of the
foundation footer must be constructed at least 42 inches below the FINISHED
grade.
Footings
shall be continuously stepped where necessary to change the elevation of
the footer. The use of lintels is not permitted.
The use of rebar reinforcement is NOT required for single-family homes
that are 3-stories or less in height.
Gravel
or other crushed stone drains shall extend at least 12-inches beyond the outside
edge of the footing and 6-inches above the top edge of the footing.
A 4-inch perforated pipe shall be placed on a minimum of 2-inches of
WASHED GRAVEL that is at least one sieve size larger than the perforations of
the pipe. The pipe and surrounding
gravel must be covered with an approved geo-textile filter membrane.
In
areas identified as having a possible high ground water table, all exterior
foundation walls that retain earth and enclose habitable or useable spaces
located below grade shall be waterproofed with a physical membrane extending
from the top of the footing to the finished grade.
CONCRETE
FLOORS & SLABS
All
concrete slab-on-ground floors shall be a minimum of 3.5 inches think.
A
four-inch base of clean sand, gravel, crushed stone (passing through a 2-inch
sieve) shall be placed on the prepared subgrade when the slab is located below
grade.
A
6 mil. Polyethylene or approved vapor retarder with joints lapped not less than
6-inches shall be placed between the concrete floor slab and the base course or
prepared subgrade.
Exterior
framed walls shall be anchored to the foundation wall by using ½ X
7 anchor bolts spaced not less than 6 feet on center.
There shall be a least two anchor bolts per plate section with one bolt
located not more than 12-inches from the end of the plate and at each corner.
ADDRESS
NUMBERS: 4-inch numbers in contrast with the background indicating the
911-building site address must be posted so as to be easily visible from the
nearest public road.
DECK ATTACHMENT TO BUILDING: ½-inch diameter hot dipped galvanized or stainless steel lag screws or carriage bolts, with washers, shall secure the ledger board to the building and be placed in accordance with Table R502.2.2.1.